Parameters in the Long parameter mode
Index Name/Selection
3015
UNDERLOAD CURVE Selects the load curve for the underload function. See parameter
1...5
3016
SUPPLY PHASE
0 = FAULT
1 = LIMIT/ALARM
2 = ALARM
3017
EARTH FAULT
0 = DISABLE
1 = ENABLE
3021
AI1 FAULT LIMIT
0.0...100.0%
Description
UNDERLOAD FUNC.
T
= nominal torque of the motor
M
ƒ
= nominal frequency of the motor (par. 9907)
N
T
M
(%)
Underload curve types
80
60
40
20
0
Number of the load curve type in the figure
Selects how the drive reacts to supply phase loss, that is when DC voltage
ripple is excessive.
The drive trips on fault
INPUT PHASE LOSS
coasts to stop when the DC voltage ripple exceeds 14% of the nominal DC
voltage.
Drive output current is limited and alarm
is generated when the DC voltage ripple exceeds 14% of the nominal DC
voltage.
There is a 10 s delay between the activation of the alarm and the output
current limitation. The current is limited until the ripple drops under the
minimum limit, 0.3 · I
.
hd
The drive generates alarm
ripple exceeds 14% of the nominal DC voltage.
Selects how the drive reacts when an earth (ground) fault is detected in the
motor or the motor cable. The protection is active only during start. An earth
fault in the input power line does not activate the protection
Note: Disabling earth (ground) fault may void the warranty.
No action
The drive trips on fault
EARTH FAULT
Defines the fault or alarm level for analog input AI1. If parameter
AI<MIN FUNCTION is set to 1 (FAULT), 2 (CONST SP 7) or 3 (LAST
SPEED), the drive generates alarm or fault
F0007), when the analog input signal falls below the set level.
Do not set this limit below the level defined by parameter
AI1.
Value in percent of the full signal range
3
2
1
ƒ
N
(code: F0022) and the motor
INPUT PHASE LOSS
INPUT PHASE LOSS
(code: A2026) when the DC
(code: F0016).
AI1 LOSS
Def
3013
1
70%
50%
5
30%
4
f
2.4 · ƒ
N
0 = FAULT
(code: A2026)
1 = ENABLE
3001
0.0%
(code:
A2006
or
1301
MINIMUM
Actual signals and parameters
111