Electric power network specification

Voltage (U
)
1
Short-circuit capacity
Frequency
Imbalance

Motor connection data

Motor type
Voltage (U
)
2
Short-circuit protection
(IEC 61800-5-1, UL 508C)
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length
Technical data
200/208/220/230/240 V AC 1-phase for 200 V AC drives
200/208/220/230/240 V AC 3-phase for 200 V AC drives
380/400/415/440/460/480 V AC 3-phase for 400 V AC drives
Regular 10% variation from converter nominal voltage is allowed as default.
Maximum allowed prospective short-circuit current at the input power connection as
defined in IEC 60439-1 and UL 508C is 100 kA. The drive is suitable for use in a circuit
capable of delivering not more than 100 kA rms symmetrical amperes at the drive
maximum rated voltage.
50/60 Hz ± 5%, maximum rate of change 17%/s
Max. ±3% of nominal phase-to-phase input voltage
AC induction motor
0 to U
, 3-phase symmetrical, U
1
The motor output is short-circuit proof by IEC 61800-5-1 and UL 508C.
Scalar control: 0...500 Hz
0.01 Hz
See section
Ratings
on page 137.
1.5 · P
N
10...500 Hz
4, 8, 12 or 16 kHz
Operational functionality and motor cable length
The drive is designed to operate with optimum performance with the following maximum
motor cable lengths. The motor cable lengths may be extended with output chokes as
shown in the table.
Frame
size
Standard drive, without external options
R0
R1...R2
With external output chokes
R0
R1...R2
at the field weakening point
max
Maximum motor cable length
m
30
50
60
100
ft
100
165
195
330