132
CODE
FAULT
F0201
DSP T1
OVERLOAD
F0202
DSP T2
OVERLOAD
F0203
DSP T3
OVERLOAD
F0204
DSP STACK
ERROR
F0206
MMIO ID ERROR
F1000
PAR HZRPM
F1003
PAR AI SCALE
Fault tracing
CAUSE
System error
Internal I/O Control board (MMIO)
fault
Incorrect speed/frequency limit
parameter setting
Incorrect analog input AI signal
scaling
WHAT TO DO
Contact your local ABB representative.
Contact your local ABB representative.
Check parameter settings. Following must apply:
2007
MINIMUM FREQ <
2008
2007
MINIMUM
FREQ/9907
and
2008
MAXIMUM
FREQ/9907
FREQ are within range.
Check parameter group
13 ANALOG INPUTS
settings. Following must apply:
1301
MINIMUM AI1 <
1302
MAXIMUM FREQ,
MOTOR NOM FREQ
MOTOR NOM
MAXIMUM AI1.