Power connections and control interfaces

The diagram gives an overview of connections. The I/O connections are
parameterable. See chapter
for the different macros and chapter
in general.
PE
L1
L2
L3
3-phase
power
supply,
200...480
V AC
Note: For 1-phase power supply, connect power to U1/L and V1/N terminals. For
connecting the power cables, see
Screen
Analog input
0...10 V
Reference voltage
+10 V DC, max. 10 mA
Aux. voltage output
+24 V DC, max. 200 mA
PROGRAMMABLE
DIGITAL INPUTS
DI5 can also be used
as a frequency input
6
FlashDrop
Input
EMC
choke
filter
Application macros
Electrical installation
Potentiometer
SCR
S1
AI
I
U
GND
AI
+10V
COM
+24 V
NC
Relay output
GND
250 V AC / 30 V DC / 6 A
NO
COM
DI1
DI2
DI3
EMC filter grounding screw
DI4
EMC
Varistor grounding screw
DI5
VAR
PE
U1
U2
V1
V2
W1
W2
Brake chopper
BRK+ BRK-
Brake resistor
Connecting the power cables
Operation principle and hardware description
on page
69
for the I/O connections
on page
39
M
3 ~
Output
AC motor
choke
on page 41.