Parameters in the Long parameter mode
Index Name/Selection
2 = 3-WIRE
3 = ALTERNATE
4 = MOTOR POT
5 = HAND/AUTO
6 = PID CONTROL
31 = LOAD FD SET
0 = USER S1 LOAD
-1 = USER S1 SAVE
-2 = USER S2 LOAD
-3 = USER S2 SAVE
-4 = USER S3 LOAD
-5 = USER S3 SAVE
Description
3-wire macro for constant speed applications
Alternate macro for start forward and start reverse applications
Motor potentiometer macro for digital signal speed control applications
Hand/Auto macro to be used when two control devices are connected to the
drive:
- Device 1 communicates through the interface defined by external control
location EXT1.
- Device 2 communicates through the interface defined by external control
location EXT2.
EXT1 or EXT2 is active at a time. Switching between EXT1/2 through digital
input.
PID control. For applications in which the drive controls a process value. For
example, pressure control by the drive running the pressure boost pump.
Measured pressure and the pressure reference are connected to the drive.
FlashDrop parameter values as defined by the FlashDrop file. Parameter
view is selected by parameter
FlashDrop is an optional device for fast copying of parameters to unpowered
drives. FlashDrop allows easy customisation of the parameter list, for
example, selected parameters can be hidden. For more information, see
MFDT-01 FlashDrop user's manual (3AFE68591074 [English]).
User 1 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
Save User 1 macro. Stores the current parameter settings and the motor
model.
User 2 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
Save User 2 macro. Stores the current parameter settings and the motor
model.
User 3 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
Save User 3 macro. Stores the current parameter settings and the motor
model.