PID control macro
This macro provides parameter settings for closed-loop control systems such as
pressure control, flow control, and so on. Control can also be switched to speed
control using a digital input. To enable the macro, set the value of parameter
APPLIC MACRO to 6 (PID CONTROL).
For the parameter default values, see section
macros
see chapter
Note: Parameter
Default I/O connections
1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(2...10 V voltage
signal).
1)
Hand: frequency reference comes from the
integrated potentiometer
PID: Process reference comes from the
integrated potentiometer.
Application macros
on page 79. If you use other than the default connections presented below,
Electrical
installation, section
2108
START INHIBIT must remain in the default setting 0 (OFF).
I/O connection
SCR
AI
GND
2)
+10V
+24V
GND
COM
DI1
DI2
DI3
DI4
DI5
Relay connection
COM
NC
NO
Default parameter values with different
I/O terminals
3)
Signal cable shield (screen)
Process actual value: 4...20 mA
Analog input circuit common
Reference voltage: +10 V DC, max. 10 mA
Auxiliary voltage output: +24 V DC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1) (Hand)
Hand (0) / PID (1) control selection
Constant speed 1: parameter
Run enable
Stop (0) / Start (1) (PID)
4)
Relay output
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
3)
Tightening torque: 0.22 N·m / 2 lbf·in
4)
Tightening torque: 0.5 N·m / 4.4 lbf·in
on page 44.
1)
1202
CONST SPEED 1
9902