Parameters in the Long parameter mode
Index Name/Selection
4023
PID SLEEP LEVEL
0.0...500.0 Hz
4024
PID SLEEP DELAY
0.0...3600.0 s
4025
WAKE-UP DEV
x...x
4026
WAKE-UP DELAY
0.00...60.00 s

99 START-UP DATA

9902
APPLIC MACRO
1 = ABB STANDARD
Actual signals and parameters
Description
Defines the start limit for the sleep function. If the motor speed is below a set
level (4023) longer than the sleep delay (4024), the drive shifts to the
sleeping mode: The motor is stopped and the control panel shows alarm
SLEEP
(code:
A2018
1)).
Parameter
4022
SLEEP SELECTION must be set to 7 (INTERNAL).
PID output level
4023
PID process feedback
PID reference
Sleep start level
Defines the delay for the sleep start function. See parameter
SLEEP LEVEL. When the motor speed falls below the sleep level, the
counter starts. When the motor speed exceeds the sleep level, the counter is
reset.
Sleep start delay
Defines the wake-up deviation for the sleep function. The drive wakes up if
the process actual value deviation from the PID reference value exceeds the
set wake-up deviation (4025) longer than the wake-up delay (4026). Wake-up
level depends on parameter
If parameter
4005
ERROR VALUE INV is set to 0:
Wake-up level = PID reference (4010) - Wake-up deviation (4025).
If parameter
4005
ERROR VALUE INV is set to 1:
Wake-up level = PID reference (4010) + Wake-up deviation (4025)
PID reference
See also figures for parameter
Unit and range depend on the unit and scale defined by parameters
WAKE-UP DELAY and
4007
Defines the wake-up delay for the sleep function. See parameter
SLEEP LEVEL.
Wake-up delay
Application macro. Definition of motor set-up data.
Selects the application macro or activates FlashDrop parameter values. See
chapter
Application macros
Standard macro for constant speed applications
t < 4024
t > 4024
4025
Stop
Start
4005
ERROR VALUE INV settings.
Wake-up level
when 4005 = 1
4025
4025
Wake-up level
when 4005 = 0
t
4023
PID SLEEP LEVEL.
UNIT SCALE.
on page 69.
Def
0.0 Hz
PID
t
4026
t
4023
PID
60.0 s
0
4026
4023
PID
0.50 s
1 = ABB
STANDARD