Parameters in the Long parameter mode
Index Name/Selection
-5 = DI5(INV)
-7 = DI1,2 (INV)
-8 = DI2,3 (INV)
-9 = DI3,4 (INV)
-10 = DI4,5 (INV)
-12 = DI1,2,3 (INV)
-13 = DI3,4,5 (INV)
1202
CONST SPEED 1
0.0...500.0 Hz
1203
CONST SPEED 2
0.0...500.0 Hz
1204
CONST SPEED 3
0.0...500.0 Hz
1205
CONST SPEED 4
0.0...500.0 Hz
1206
CONST SPEED 5
0.0...500.0 Hz
1207
CONST SPEED 6
0.0...500.0 Hz
1208
CONST SPEED 7
0.0...500.0 Hz
Description
Speed defined by parameter
inverted digital input DI5. 0 = active, 1 = inactive.
Constant speed selection through inverted digital inputs DI1 and DI2.
1 = DI active, 0 = DI inactive.
DI1 DI2 Operation
1
1 No constant speed
0
1 Speed defined by parameter
1
0 Speed defined by parameter
0
0 Speed defined by parameter
See selection DI1,2 (INV).
See selection DI1,2 (INV).
See selection DI1,2 (INV).
Constant speed selection through inverted digital inputs DI1, DI2 and DI3.
1 = DI active, 0 = DI inactive.
DI1 DI2 DI3 Operation
1
1
1 No constant speed
0
1
1 Speed defined by parameter
1
0
1 Speed defined by parameter
0
0
1 Speed defined by parameter
1
1
0 Speed defined by parameter
0
1
0 Speed defined by parameter
1
0
0 Speed defined by parameter
0
0
0 Speed defined by parameter
See selection DI1,2,3(INV).
Defines constant speed 1 (that is drive output frequency).
Output frequency
Defines constant speed 2 (that is drive output frequency).
Output frequency
Defines constant speed 3 (that is drive output frequency).
Output frequency
Defines constant speed 4 (that is drive output frequency).
Output frequency
Defines constant speed 5 (that is drive output frequency).
Output frequency
Defines constant speed 6 (that is drive output frequency).
Output frequency
Defines constant speed 7 (that is drive output frequency). Note that constant
speed 7 may be used also as jogging speed
fault function
3001
AI<MIN FUNCTION.
Output frequency
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1205
CONST SPEED 4
1206
CONST SPEED 5
1207
CONST SPEED 6
1208
CONST SPEED 7
(1010
JOGGING SEL) and with
Def
E: 5.0 Hz /
U: 6.0 Hz
E: 10.0 Hz /
U: 12.0 Hz
E: 15.0 Hz /
U: 18.0 Hz
E: 20.0 Hz /
U: 24.0 Hz
E: 25.0 Hz /
U: 30.0 Hz
E: 40.0 Hz /
U: 48.0 Hz
E: 50.0 Hz /
U: 60.0 Hz