Default I/O Connection Diagram - ABB ACS150 series User Manual

0.37...4kw; 0.5...5 hp
Hide thumbs Also See for ACS150 series:
Table of Contents

Advertisement

46

Default I/O connection diagram

The default connection of the control signals depends on the application macro in
use, which is selected with parameter
The default macro is the ABB standard macro. It provides a general purpose I/O
configuration with three constant speeds. Parameter values are the default values
given in section
information on other macros, see chapter
The default I/O connections for the ABB standard macro are given in the figure
below.
1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(0...10 V voltage
signal).
1) See parameter group
DI3 DI4 Operation (parameter)
0
0 Set speed through integrated
potentiometer
0 Speed 1
1
0
1 Speed 2
1 Speed 3
1
Electrical installation
Default parameter values with different macros
I/O connection
SCR
AI
GND
3)
+10V
+24V
GND
COM
DI1
DI2
DI3
DI4
DI5
Relay connection
COM
NC
NO
12 CONSTANT
SPEEDS:
(1202 CONST SPEED
1)
(1203 CONST SPEED
2)
(1204 CONST SPEED
3)
9902
APPLIC MACRO.
Application macros
4)
Signal cable shield (screen)
Frequency reference: 0...20 mA
Analog input circuit common
Reference voltage: +10 V DC, max. 10 mA
Auxiliary voltage output: +24 V DC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant speed selection
Constant speed selection
Acceleration and deceleration selection
5)
Relay output
No fault [Fault (-1)]
2) 0 = ramp times according to parameters
ACCELER TIME 1 and
1 = ramp times according to parameters
ACCELER TIME 2 and
3) 360 degree grounding under a clamp.
4) Tightening torque: 0.22 N·m / 2 lbf·in
5) Tightening torque: 0.5 N·m / 4.4 lbf·in
on page 79. For
on page 69.
1)
1)
2)
2202
2203
DECELER TIME 1.
2205
2206
DECELER TIME 2.