Huawei SmartLogger2000 User Manual page 120

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000
User Manual
No.
Parameter
3
PQ mode
4
Auto start
upon grid
recovery
Grid
5
connection
duration after
power grid
recovery
6
Grid
reconnection
voltage upper
limit
7
Grid
reconnection
voltage lower
limit
Issue 04 (2018-04-10)
Description
If PQ mode 1 is selected,
the maximum AC output
power equals the
maximum apparent power.
If PQ mode 2 is selected,
the maximum AC output
power equals the rated
output power.
Specifies whether to allow
the inverter to
automatically start after
the power grid recovers.
Specifies the waiting time
for inverter restart after the
power grid recovers.
The standards of certain
countries and regions
require that the inverter
must not connect to the
power grid when the
power grid voltage is
higher than the upper
limit.
The standards of certain
countries and regions
require that the inverter
must not connect to the
power grid when the
power grid voltage is
lower than the lower limit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
N/A
SUN2000-36K
TL: (Pmax = 40
kW) and PQ
mode 2 (Pmax
= 36 kW)
SUN2000-42K
TL: PQ mode 1
(Pmax = 47
kW) and PQ
mode 2 (Pmax
= 42 kW)
SUN2000-50K
TL-M0 and
SUN2000-60K
TL-M0: PQ
mode 1 and PQ
mode 2
N/A
Disable
Enable
s
[0, 900]
V
[100%Vn,
136%Vn]
V
[45%Vn, 95%Vn]
7 WebUI
Remarks
This parameter is
supported by the
SUN2000-36KTL,
SUN2000-42KTL,
SUN2000-50KTL-M0,
and
SUN2000-60KTL-M0.
This parameter is set to
Disable by default if
the Japanese grid code
is selected.
The value range is [150,
900] if the Japanese
grid code is selected.
Vn represents the rated
voltage.
110