User Manual
Alarm
Alarm
Alarm
ID
Name
Severity
1107–1
DI1
Major
114
custom
alarm–D
I8
custom
alarm
24V
1115
Major
power
failure
Issue 04 (2018-04-10)
Alarm
Cause
Sub-ID
1
The dry contact
signal from the
peripheral to the
corresponding
DI port on the
SmartLogger is
abnormal.
The 24 V power
1
module in the
smart array
controller is
faulty.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Device Maintenance
Measures
Check the DI port cable connection. If
the cable is loose, disconnected, or
connected in reserve, reconnect it
securely.
Verify that the relevant device works
properly.
Check whether the cable to the 24 V
power module in the smart array
controller is loose, disconnected, or
connected in reverse. If so, reconnect
the cable securely.
Check whether the 24 V power module
in the smart array controller is faulty.
Replace the faulty power module.