8.3.3 Reactive Power Fix Control

If the PV plant is required to generate at the grid-tied point specified constant reactive power
within the power factor range, set Reactive power control mode to Reactive power fix
control.
Issue 04 (2018-04-10)
A maximum of 16 levels are supported for power factors.
"√" indicates a low level. When connecting to GND2, the four DI ports of the SmartLogger are
low-level ports. If not connected, the ports are high-level ports.
The percentage levels of DI5–DI8 should differ from each other. Otherwise, an abnormal command
is generated.
If the actual input DI signal is inconsistent with that configured on the WebUI, the SmartLogger
does not allow the inverter to generate reactive power and the Abnormal Reactive Schedule alarm
is generated.