No.
Parameter
9
Voltage rise
suppression
10
Voltage rise
suppression
reactive
adjustment
point
Voltage rise
11
suppression
active
derating point
Frequency
12
change rate
protection
13
Frequency
change rate
protection
point
Frequency
14
change rate
protection
time
15
Soft start
time after
grid failure
Issue 04 (2018-04-10)
Description
The standards of certain
countries and regions
require that the active
power of the inverter be
derated according to a
certain gradient when the
output voltage exceeds a
certain value.
The standards of certain
countries and regions
require that the inverter
must generate a certain
amount of reactive power
when the output voltage
exceeds a certain value.
The standards of certain
countries and regions
require that the active
power of the inverter be
derated according to a
certain gradient when the
output voltage exceeds a
certain value.
The inverter triggers
protection when the power
grid frequency changes too
fast.
Specifies the frequency
change rate protection
threshold.
Specifies the frequency
change rate protection
duration.
Specifies the time for the
power to gradually increase
when the inverter restarts
after the power grid
recovers.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
N/A
Disable
Enable
%
[100, 115]
%
[100, 115]
N/A
Disable
Enable
Hz/s
1100 V inverter:
[0.1, 5]
Others: [0.1,
2.5]
s
[0.2, 20.0]
s
[20, 800]
7 WebUI
Remarks
This parameter is set to
Enable by default if
the Italian grid code
CEI0-16 is selected.
This parameter is
displayed when
Voltage rise
suppression is set
to Enable.
The value of
Voltage rise
suppression active
derating point
must be greater
than that of
Voltage rise
suppression
reactive
adjustment point.
N/A
This parameter is
displayed if
Frequency change
rate protection is set
to Enable.
This parameter is
displayed if
Frequency change
rate protection is set
to Enable.
This parameter is set to
360 by default if the
Australian AS4777
grid code is selected,
and to 300 by default if
the Brazilian ABNT
NBR 16149 or South
African SA_RPPs grid
code is selected.
118