Huawei SmartLogger2000 User Manual page 126

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000
User Manual
No.
Parameter
46
Level-3 UF
protection
47
Level-3 UF
protection
time
Level-4 UF
48
protection
49
Level-4 UF
protection
time
Level-5 UF
50
protection
51
Level-5 UF
protection
time
52
Level-6 UF
protection
53
Level-6 UF
protection
time
Feature Parameters
Table 7-8 Parameter description
No.
Parameter
1
LVRT
Issue 04 (2018-04-10)
Description
Specifies the level-3
underfrequency
protection threshold.
Specifies the level-3
underfrequency
protection duration.
Specifies the level-4
underfrequency
protection threshold.
Specifies the level-4
underfrequency
protection duration.
Specifies the level-5
underfrequency
protection threshold.
Specifies the level-5
underfrequency
protection duration.
Specifies the level-6
underfrequency
protection threshold.
Specifies the level-6
underfrequency
protection duration.
Description
When the power grid
voltage is abnormally low
for a short time, the
inverter cannot disconnect
from the power grid
immediately and has to
work for some time. This is
called LVRT.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
Hz
[0.85xFn, 1xFn]
ms
[50, 7200000]
Hz
[0.85xFn, 1xFn]
ms
[50, 7200000]
Hz
[0.85xFn, 1xFn]
ms
[50, 7200000]
Hz
[0.85xFn, 1xFn]
ms
[50, 7200000]
Unit
Value Range
N/A
Disable
Enable
7 WebUI
Remarks
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Remarks
This parameter is set to
Enable by default if
the German
BDEW-MV grid code
is selected.
116