Figure 7-69 Setting export limitation parameters
Parameter
Power Meter
Electric meter power
direction
Maximum grid feed-in
power
Issue 04 (2018-04-10)
Description
If Export Limitation is
set to Enable, set Power
Meter to Smart meter.
Otherwise the export
limitation would not take
effect.
When the inverter does
not have output power,
set Electric meter power
direction to Positive if
the active power
displayed on the meter is
positive. Otherwise set it
to Reverse.
Setting the maximum
power that the inverter
can transport to the power
grid.
Suggestion: Set this
parameter based on the
countercurrent threshold
allowed by the power
grid company.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Parameter
Maximum protection
time
Power raising threshold
Power limit for abnormal
electric meter
7 WebUI
Description
Setting the maximum
duration from the time
the SmartLogger detects
countercurrent to the time
it controls the inverter
output power to reach 0.
Suggestion: Set this
parameter based on the
maximum countercurrent
duration allowed by the
power grid company.
Setting the inverter
output power raising
threshold.
Setting the inverter
output power percentage
controlled by the
SmartLogger when
communication between
the SmartLogger and the
power meter is abnormal.