No.
Parameter
8
Grid
reconnection
frequency
upper limit
9
Grid
reconnection
frequency
lower limit
Reactive
10
power
compensation
(cosψ-P)
trigger
voltage
11
Reactive
power
compensation
(cosψ-P) exit
voltage
12
Isolation
Protection Parameters
Table 7-7 Parameter description
No.
Parameter
1
Unbalance
voltage
protection
Issue 04 (2018-04-10)
Description
The standards of certain
countries and regions
require that the inverter
must not connect to the
power grid when the
power grid frequency is
higher than the upper
limit.
The standards of certain
countries and regions
require that the inverter
must not connect to the
power grid when the
power grid frequency is
lower than the lower limit.
Specifies the voltage
threshold for triggering
reactive power
compensation when LVRT
occurs.
Specifies the voltage
threshold for exiting
reactive power
compensation when the
inverter recovers from
LVRT.
Specifies the inverter
working mode based on
the grounding status at the
DC side and the
connection to the power
grid.
Description
Specifies the inverter
protection threshold in
the case of unbalanced
power grid voltage.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
Hz
[100%Fn, 112%Fn]
Hz
[85%Fn, 100%Fn]
%
[100, 110]
%
[90, 100]
N/A
Input grounded
(with TF)
Input
ungrounded
(without TF)
Input
ungrounded
(with TF)
Unit
Value Range
%
[0.0, 50.0]
7 WebUI
Remarks
Fn represents the rated
frequency.
N/A
N/A
N/A
Remarks
N/A
111