7.8.3.4 Setting a Tracking System

If a PV string uses a tracking system with controllers, you can set parameters for the tracking
system over the WebUI.
Because of permission restriction, log in as Advanced User. Choose Monitoring >
SUN2000 > Tracking System to access the target page.
Issue 04 (2018-04-10)
Description
Specifies the output upper
threshold for the
maximum active power to
adapt to various market
requirements.
If this parameter is set to
Enable, the inverter shuts
down after receiving the
0% power limit
command. If this
parameter is set to
Disable, the inverter does
not shut down after
receiving the 0% power
limit command.
Adjusts the inverter
output reactive power.
In some specific
application scenarios, a
power grid company
requires that the inverter
can perform reactive
power compensation at
night to ensure that the
power factor of the local
power grid meets
requirements.
The parameters vary depending on the controller manufacturer. Set parameters based on site
requirements.
This function is applicable only to 1100 V and 1500 V inverters.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
kW
[0.1, Pmax_limit]
N/A
Disable
Enable
N/A
(-1.000, 1.000]
N/A
Disable
Enable
7 WebUI
Remarks
N/A
N/A
This parameter is for
the
SUN2000-100KTL-
USH0 only and
displayed when
Remote power
schedule is set to
Enable.
This parameter is
available only when
Isolation is set to
Input ungrounded
(with TF).