7.10.7 Setting DI Parameters

You can set parameters for DI ports over the WebUI.
The SmartLogger provides eight DI ports, that is, DI1(GND1) to DI4(GND1) and DI5(GND2)
to DI8(GND2). For the connection method, see
Because of permission restriction, log in as Special User. Choose Settings > DI to access the
target page.
Figure 7-66 Setting DI parameters
Issue 04 (2018-04-10)
If Cubicle alarm enabling is set to Enable, the Abnormal Cubicle alarm is generated when the dry
contact signal is effective and the Cubicle is abnormal.
When a valid level is delivered into a DI port, an alarm is generated. You can set the
alarm name and severity.
A DI port shuts down the inverter using OVGR signals.
If a DI port is activated, it cannot be set again under Dry contact remote control in
Shutdown over Dry Contacts
Shutdown over Dry Contacts
Scheduling, it cannot be set here again.
Activation Status: If the DI port is set to Activated, you can set the function of this DI
port. If the DI port is not set to Activated, you cannot set the function of this DI port.
Dry Contact Status can be set to Open or Close. If Activation Status is set to
Activated and Dry Contact Status is set to Close, it means that only when the DI port is
set to Close, the SmartLogger sends the inverter remote shutdown command.
If the SmartLogger connects to inverters over dry contacts and Trigger Shutdown is set
to Enable, the SmartLogger shuts down the inverters over OVGR signals.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4.10 Connecting a Ripple Control
and
8 Power Grid
Scheduling. If a DI port has been set in
or has been set to Dry contact remote control in
7 WebUI
Receiver.
7.10.6 Remote
7.10.6 Remote
8 Power Grid
168

Advertisement

Table of Contents
loading

Table of Contents