Siemens LMV5 Series Basic Documentation page 111

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
90°
Pos.
0 %
7550d09E
Change of load / position with several points
Using this method, up to 15 points can be defined.
6. Shutdown
On the menu: «Params & Display» → «Ratio Control» → «Settings Gas / Oil»
→ «Special Positions» → «Autom / Manual / Off»
or on:
«Manual Operation»
and confirm
7. Setting the postpurge positions
The system shuts down and stops in phase «Driving to postpurge 72».
Now, the postpurge positions on menu «Special positions» can be set.
Then, on «Program Stop», set to «deactivated».
The system continues the shutdown sequence and stops in phase «Standby 12».
Basic Documentation LMV51...
7 Display and operating unit AZL5...
AIR
FUEL
AUX
100 %
Load
«Autom / Manual / Off» to «Burner off»
111/278
CC1P7550en
01.10.2003