Siemens LMV5 Series Basic Documentation page 172

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Connection symbol
X3-01
PIN1
PIN2
X3-02
PIN1
PIN2
X3-03
PIN1
PIN2
X3-04
PIN1
PIN2
PIN3
PIN4
PIN5
X4-01
PIN1
PIN2
PIN3
PIN4
X4-02
PIN1
PIN2
PIN3
X4-03
PIN1
PIN2
PIN3
X5-01
PIN1
PIN2
PIN3
X5-02
PIN1
PIN2
PIN3
X5-03
PIN1
PIN2
PIN3
PIN4
172/278
Siemens Building Technologies
HVAC Products
10
Description of the connection terminals
Description
x
Fan motor contactor
x
Alarm
x
Air pressure switch (LP)
x
Power signal for air pressure switch
(LP)
x
End switch burner flange
x
Power signal for end switch burner
flange
x
Safety loop
x
Power signal for safety loop
x
Protective earth (PE)
x
Neutral conductor (N)
x
Live conductor (L)
Fuel selection "internal" if pin 1-2 is not
used
x
Fuel selection gas
x
Fuel selection oil
x
Fan contactor contact (FCC) or FGR-
PS
x
Reset / manual lockout
x
Protective earth (PE)
x
Neutral conductor (N)
x
Ignition
x
Protective earth (PE)
x
Neutral conductor (N)
x
Start signal or PS relief (APS test valve) AC 230 V +10 % / -15 %, 50...60 Hz,
x
Protective earth (PE)
x
Pressure switch min-oil (DWmin-oil)
x
Power signal for pressure switch-min-oil
(DWmin-oil)
x
Protective earth (PE)
x
Pressure switch-max-oil (DWmax-oil)
x
Power signal for pressure switch-max-
oil (DWmax-oil)
x
Controller (ON / OFF)
x
Controller closes / stage 3
x
Controller opens / stage 3
x
Power signal for control of controller
Basic Documentation LMV51...
10 Description of the connection terminals
Electrical rating
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 5 A
AC 230 V +10 % / -15 %, 50...60 Hz,
fuse 6.3 AT
(DIN EN 60 127 2 / 5)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos ϕ 0.2
0.5 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
CC1P7550en
01.10.2003