Siemens LMV5 Series Basic Documentation page 228

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
AB
1B
O2M
AB
20
O2M
AB
21
O2M
AB
22
O2M
AB
23
O2M
AB
24
O2M
AB
25
O2M
AB
30
O2M
AB
31
O2M
AB
32
O2M
228/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault O2 Module
Fault ADC test voltages
O2 Sensor Temp too low
Temperature of QGO measuring cell too
low
O2 Sensor Temp too high
Temperature of QGO measuring cell too
high
Internal Fault O2 Module
Fault during calculation test
Unplaus Value Ri 02 Measuring
Measured internal resistance of the QGO
Cell
measuring cell is smaller than 5 Ohm or
greater than 150 Ohm
Response Time O2 Measuring
Measured response time of the QGO
Cell too long
measuring cell exceeds 5 s
O2 Sensor Test aborted by O2
Fault occurred during O2 sensor test
Module
Internal Fault O2 Module
CAN fault
Internal Fault O2 Module
CRC fault of a parameter page
Internal Fault O2 Module
Page too long open
Meaning for the LMV5x system
Troubleshooting
*2)
Check mains power supply on O2 module.
Check fuse F2 on O2 module.
Check connection between O2 module and QGO heating
Check QGO temperature
*2)
Check electrical connection (polarity, short-circuit).
If fault occurs after more than 1 year, QGO may have
reached the end of its service life -> replace
Check mounting position of QGO.
Check to see if QGO is dirty.
If error occurs after more than 1 year, QGO may have
reached end of its service life -> replace
Check fluctuations of the O2 value
*2)
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5...
parameters.
Otherwise, replace defective O2 module
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL5...
parameters.
Otherwise, replace defective O2 module
CC1P7550en
01.10.2003