Siemens LMV5 Series Basic Documentation page 174

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Description of the connection terminals (cont'd)
Connection symbol
X9-01
X9-02
X9-03
X10-01
X10-02
X10-03
174/278
Siemens Building Technologies
HVAC Products
Description
PIN4
x
Fuel valve V1 (gas)
PIN3
x
Fuel valve V2 (gas)
PIN2
x
Fuel valve PV (gas)
PIN1
x
Fuel valve SV (gas)
PIN2
x
Protective earth (PE)
PIN1
x
Neutral conductor (N)
PIN4
x
Pressure switch-min-gas, start release
gas
PIN3
x
Pressure switch-max-gas (DWmax-gas) AC 230 V +10 % / -15 %, 50...60 Hz,
PIN2
x
Pressure switch-VP-gas / LT or valve
closing contact (CPI)
PIN1
x
Power signal for pressure switch
PIN4
x
Neutral conductor (N)
PIN3
x
Power signal transformer
PIN2
x
AC power signal GO
PIN1
x
AC power signal G
PIN6
x
QRI... (IR detector) signal voltage
PIN5
x
Protective earth (PE)
PIN4
x
Neutral conductor (N)
PIN3
x
Power signal
PIN2
x
QRI... (IR detector) power supply
PIN1
x
QRB... signal voltage
PIN1
x
Ionization probe
Basic Documentation LMV51...
10 Description of the connection terminals
Electrical rating
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos ϕ 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
max 1 mA
AC 12 V +10 % / -15 %, 50...60 Hz,
max 1.2 mA
Umax DC 5 V
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
DC 14 / 21 VC
Imax 100 mA
max. DC 8 V
Umax (X3-04-PINS)
Imax. 0.5 mA
CC1P7550en
01.10.2003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents