Siemens LMV5 Series Basic Documentation page 232

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
D3
#
O2
01
D3
O2
02
D3
O2
03
D3
O2
E1
-
FuM
E3
-
O2
F0
-
BU
F1
#
BU
01
F1
BU
02
F1
BU
03
F1
BU
04
F1
BU
05
F1
BU
06
F1
BU
232/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Fault Feedback O2 Module
Basic unit has detected a wrong stage of
the O2 module
Fault Feedback O2 Module
CRC error
Fault Feedback O2 Module
Key error main loop counter
Fault Feedback O2 Module
No feedback for max. number
Fault Feedback VSD Module
Basic unit has detected a ROM-CRC fault
in the VSD module when checking its
feedback signal
Fault Feedback O2 Module
Basic unit has detected a ROM-CRC fault
in the O2 module when checking its
feedback signal
Internal Fault Basic Unit
Plausibility fault during calculation of
interpolation values
Internal Fault Basic Unit
Internal fault during calculation of
precontrol
Internal Fault Basic Unit
Internal Fault Basic Unit
Internal Fault Basic Unit
Internal Fault Basic Unit
Internal Fault Basic Unit
Internal Fault Basic Unit
Internal fault calculation of precontrol.
Undefined value in the curves used for the
calculation
Meaning for the LMV5x system
Troubleshooting
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective module
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective module
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective module
*1)
Check curve setting, check fuel parameters depending on
the selected type of fuel
CC1P7550en
01.10.2003