Siemens LMV5 Series Basic Documentation page 211

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
01
86
LC
02
86
LC
03
86
LC
87
#
ABE
01
87
ABE
02
87
ABE
03
87
ABE
88
#
All
01
88
SA
02
88
LC
03
88
ABE
04
88
FuM
05
88
O2M
90
-
SA
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Fault Feedback Load Controller
CRC error
Fault Feedback Load Controller
Key error main loop counter
Fault Feedback Load Controller
No feedback for max. number
Fault Feedback AZL
Basic unit has detected wrong state of the
AZL...
Fault Feedback AZL5...
CRC error
Fault Feedback AZL5...
Key error main loop counter
Fault Feedback AZL5...
No feedback for max. number
Plausibility fault NMT
Fault Feedback Actuator
Undefined fault class of SA
Fault Feedback Load Controller
Undefined fault class of LC
Fault Feedback AZL
Undefined fault class of AZL
Fault Feedback VSD Module
Undefined fault class of VSD module
Fault Feedback O2 Module
Undefined fault class of O2 module
Fault Feedback Aux Actuator 3
Basic unit has detected a ROM-CRC error
on the air actuator when checking its
feedback signal
Meaning for the LMV5x system
Troubleshooting
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the faulty ABE
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective AZL...(see
diagnostic code) or basic unit
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
211/278
CC1P7550en
01.10.2003