Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Air Press Switch connected but
APS connected but deactivated
deactivated
FCC / FGR – APS connected but
FCC / FGR – APS connected but
deactivated
deactivated
Gas Pressure min connected but
GP-Min connected but deactivated
deactivated
Gas Pressure max connected
GP-Max connected but deactivated
but deactivated
Oil Pressure min connected but
OP-Min connected but deactivated
deactivated
Oil Pressure max connected but
OP-Max connected but deactivated
deactivated
Start Signal Oil connected but
Start signal oil connected but deactivated
deactivated
HO Start connected but
HO start connected but deactivated
deactivated
Start Signal Gas connected but
Start signal gas connected but deactivated
deactivated
Locked by SLT
Shutdown via SLT test
Programstop active
Program stop was activated. System has
stopped at the parameterized position
Programstop active
Program stop "STOP_DR_PREP" in
Phase 24 active
Programstop active
Program stop "STOP_PREP2" in Phase
32 active
Programstop active
Program stop "STOP_DR_IGN" in Phase
36 active
Programstop active
Program stop "STOP_INTERV1" in Phase
44 active
Programstop active
Program stop "STOP_INTERV2" in Phase
52 active
Meaning for the LMV5x system
Troubleshooting
SLT was activated and safety shutdown was triggered
(usually via the SLT)
Deactivate the program stop if no longer required
CC1P7550en