External predefined load,
multistage
External setpoint
changeover
External setpoints or
predefined load via
digital e-bus interface
Siemens Building Technologies
HVAC Products
Stage 1
I (mA)
5
U (V)
2.5
Detection of short-circuits and open-circuits of lines is ensured - similar to the sensor
inputs.
In operating mode 2 (intLC), changeover between the 2 internally defined setpoints W1
and W2 can be accomplished by means of an external (potentialfree) contact.
The settings described under «Input 3» can also be made from a BMS connected to the
AZL5... via RS-232 and bus interface.
Parameter:
LC_OptgMode (intLC o.DDC / extLC o.DDC)
An external predefined setpoint via e-bus exists with «Int LC bus».
An external predefined load via e-bus exists with «Ext LC bus».
Basic Documentation LMV51...
6 Temperature or pressure controller (internal load controller LC)
Stage 2
Stage 3
10
15
5
7.5
81/278
CC1P7550en
01.10.2003