Siemens LMV5 Series Basic Documentation page 195

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
15
04
SA
15
08
SA
15
10
FuM
15
20
SA
16
#
BU
16
00
BU
16
01
BU
16
02
BU
16
03
BU
16
04
BU
16
05
BU
16
0A
BU
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Fault Positioning Actuator
Positioning fault auxiliary actuator 1
Fault Positioning Actuator
Positioning fault auxiliary actuator 2
Fan Speed not reached
The fan in combination with the VSD has
not reached the required speed
Fault Positioning Actuator
Positioning fault auxiliary actuator 3
Internal Fault Basic Unit
Basic unit has detected a plausibility fault
in the ratio control system.
The diagnostic code describes the cause
of the fault.
Internal Fault Basic Unit
Ratio curve of the air actuator is not fully
defined
Internal Fault Basic Unit
Ratio curve of the fuel actuator is not fully
defined
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 1 is not
fully defined
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 2 is not
fully defined
Internal Fault Basic Unit
Ratio curve of auxiliary actuator 3 is not
fullydefined
Internal Fault Basic Unit
VSD curve is not fully defined
Internal Fault Basic Unit
Calculated P-part outside the permissible
range
Meaning for the LMV5x system
Troubleshooting
Check the curve to see if correct values have been entered
for the air actuator. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for the fuel actuator. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for auxiliary actuator 1. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for auxiliary actuator 2. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for auxiliary actuator 3. Readjust the ratio curve, if required
Check the curve to see if correct values have been entered
for the VSD. Readjust the ratio curve, if required
Check to see if correct values have been entered for the
controller parameters. Readjust O2 trim control, if required,
or repeat the settings
195/278