Siemens LMV5 Series Basic Documentation page 124

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1
Menu level 2
Menu level 3
Configuration
124/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
DelayStartPrev
PostpurgeLocko
ut
MaxTmeStartRel
ConfigGeneral
AlarmStartPrev
NormDirectStart
OilPumpCouplin
g
IgnOilPumpStart
ForcedIntermit
ContinuousPurg
e
FuelTrainGas
FuelTrainOil
FuelTrainReset
FuelTrainGas
FuelTrainOil
MainsFrequency
ConfigIn/Output
Description
Time until message on start prevention and heat demand is
delivered
Postpurge in lockout position
Maximum phase time start release (timeout)
General parameters of burner control
With/without alarm in the event of start prevention and heat
demand
Normal/direct start in the event of heat demand in phase 78
Configuration for coupling the oil pump
Switch-on time of ignition and oil pump
With / without forced intermittent operation
Configuration for normal or continuous fan operation
Fuel train when firing on gas
Fuel train when firing on oil
Resetting the fuel train to invalid value
Selection of mains frequency 50 Hz/60 Hz
Configuring the inputs and outputs
Value range
Access
Default
LMV51 LMV52
rights
parameter
setting
0.4..630 s
Service
35s
x
0.2..63 min
OEM
0.2s
x
0.2..630 s
OEM
120s
x
Service
x
Service
x
deactivated
Service
deactivated
x
activated
NormalStart
OEM
NormalStart
x
DirectStart
Magnetcoupl
OEM
Magnetcoup
x
Directcoupl
l
on in Ph38
OEM
on in Ph38
x
on in Ph22
deactivated
Service
activated
x
activated
deactivated
OEM
deactivated
x
activated
DirectIgniG
OEM
invalid
x
Pilot Gp1
Pilot Gp2
LightOilLO
OEM
invalid
x
HeavyOilHO
LO w Gasp
HO w Gasp
OEM
x
OEM
x
OEM
x
50 Hz
OEM
50 Hz
x
60 Hz
OEM
x
CC1P7550en
01.10.2003
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Hide quick links:

Advertisement

Table of Contents
loading