Siemens LMV5 Series Basic Documentation page 227

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A9
1F
FuM
AB
#
O2M
AB
01
O2M
AB
02
O2M
AB
04
O2M
AB
05
O2M
AB
07
O2M
AB
08
O2M
AB
09
O2M
AB
0A
O2M
AB
10
O2M
AB
12
O2M
AB
13
O2M
AB
15
O2M
AB
16
O2M
AB
17
O2M
AB
18
O2M
AB
19
O2M
AB
1A
O2M
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault VSD Module
Internal plausibility fault. This type of fault
detects faults that cannot practically
occur...
Fault O2 Module
The O2 module has detected own fault
and reported it to the basic unit
Internal Fault O2 Module
CRC fault during ROM test
Internal Fault O2 Module
CRC fault during RAM test
Internal Fault O2 Module
Fault during key value check
Internal Fault O2 Module
Error code for time block overflow
Internal Fault O2 Module
Sync fault or CRC fault
Internal Fault O2 Module
Error code for main loop counter
Internal Fault O2 Module
Fault during stack test
Internal Fault O2 Module
Feedback values invalid
Unplaus Value Nernst Voltage
Nernst voltage outside the valid range
O2 Module
Unplaus Value Thermocouple
Thermocouple voltage outside the valid
O2 Module
range
Unplaus Value Compensation
Compensation element voltage outside
Element
the valid range
Unplaus Value Flue Gas Temp
Temperature of combustion air sensor
O2 Module
outside the valid range (-20...+400 °C)
Unplaus Value Flue Gas Temp
Temperature of flue gas sensor outside
O2 Module
the valid range (-20...+400 °C)
Internal Fault O2 Module
Fault during combustion air temperature
sensor test
Internal Fault O2 Module
Fault during thermocouple test
Internal Fault O2 Module
Fault during compensation element test
Internal Fault O2 Module
Fault during channel comparison of O2
signal
Meaning for the LMV5x system
Troubleshooting
*1)
*2)
*2)
*2)
*2)
*2)
*2)
*2)
*2)
Check the connection (correct polarity, short-circuit)
Check connections (polarity, short-circuit, open-circuit).
Check power supply to the O2 module.
Check fuse F2 on the O2 module.
Check heating control on the QGO.
Check connections (polarity, short-circuit, open-circuit).
Check housing temperature of the QGO (temperature inside
-25°C..120°C)
Check connections (short-circuit, open-circuit).
Check ambient temperature
Check connections (short-circuit, open-circuit).
Check ambient temperature
*2)
*2)
*2)
*2)
227/278