Siemens LMV5 Series Basic Documentation page 269

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
Linear progression of O
The O
value between the curvepoints should progress in a linear fashion. To
2
make checks, approach load positions between the curvepoints and check the O
value. If the progression is not linear, additional curvepoints should be set and the
O
progression should be appropriately corrected.
2
O
(%)
2
linear (guter O
6
5
O
-Verbund
4
2
3
2
1
Checking the transfer range between damper and VSD
When using several air-influencing actuators (e.g. air damper or VSD), it should be
made certain that the curves are as smooth as possible. Irregularities should be
avoided.
O
(%)
2
____ Good
------ Poor
Basic Documentation LMV51...
18 Addendum 4: LMV52... with O2 trim control and O2 module
value between the curvepoints
2
-Verlauf)
2
nicht linear (schlechter O
zusätzliche Stützpunkte setzen
100 %
Frequenzumrichter
Klappe
Leistung (%)
-Verlauf)
2
Leistung (%)
CC1P7550en
2
269/278
01.10.2003