Siemens LMV5 Series Basic Documentation page 196

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
16
0B
BU
16
0C
BU
16
0D
BU
16
0E
BU
16
0F
BU
16
03
BU
16
14
BU
16
20
BU
16
21
BU
16
22
BU
16
23
BU
196/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault Basic Unit
Calculated I-part outside the permissible
range
Internal Fault Basic Unit
Calculated system delay time outside the
permissible range
Internal Fault Basic Unit
Calculated O2 setpoint outside the
permissible range
Internal Fault Basic Unit
Calculated O2 min. value outside the
permissible range
Internal Fault Basic Unit
Calculated O2 ratio value outside the
permissible range
Internal Fault Basic Unit
The load / point number predefined by the
AZL... lies outside the permissible range
Internal Fault Basic Unit
Calculated standardized value lies outside
the permissible range
Internal Fault Basic Unit
With hysteresis compensation: Permissible
target positioning range exceeded
Internal Fault Basic Unit
The load / point number predefined by the
AZL... lies outside the permissible range
Internal Fault Basic Unit
With a switch instruction, none of the
defined cases was satisfied
Internal Fault Basic Unit
With the switch instruction, no defined ratio
control phase has been identified
Meaning for the LMV5x system
Troubleshooting
Check to see if correct values have been entered for the
controller parameters. Readjust O2 trim control, if required,
or repeat the settings
Check to see if correct values have been entered for the
controller parameters. Readjust O2 trim control, if required,
or repeat the settings
Check to see if correct values have been entered for the O2
setpoints. Readjust O2 trim control, if required, or repeat
the settings
Check to see if correct values have been entered for the O2
min. values. Readjust O2 trim control, if required, or repeat
the settings
Check to see if the correct values have been entered for the
O2 ratio values. Readjust O2 trim control, if required, or
repeat the settings
*1)
Check if the correct values have been entered for the
standardized values. Readjust O2 trim control, if required,
or repeat the settings
*1)
*1)
*1)
*1)
CC1P7550en