Siemens LMV5 Series Basic Documentation page 144

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1
Menu level 2
Menu level 3
SystemConfig
LC_OptgMode
Ext Inp X62 U/I
TempLimiter
O2Ctrl/LimitrGas
O2Ctrl/LimitrGas
144/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
TL_Thresh_Off
TL_SD_On
Sensor Select
MeasureRangeP
tNi
Description
Settings for LMV5x system configuration
Operating mode with load controller
Configuration of external input X62
Temperature limiter OFF threshold, in °C
Temperature limiter switching differential ON
Select actual value input
E1-> Pt100, TL act.
E4-> Pt1000, TL act.
E4-> Ni1000, TL act.
E2-> Temp, TL inact.
E2-> Pressure, TL inact.
E1-> Pt100 for controller + TL and E4-> Pt1000 for TL
E1-> Pt100 for controller + TL and E4-> Ni1000 for TL
No input
End of measurement range for sensor at input X60
Operating mode of O2 controller / limiter when firing on gas
Operating mode of O2 controller / limiter when firing on oil
Value range
Access
Default
rights
parameter
setting
User
ExtLC X5-03
User
IntLC
IntLC
IntLC Bus
IntLC X62
ExtLC X62
ExtLC Bus
4..20 mA
Service
4..20 mA
0/2..10 V
Service
0..2000 °C
Service
95°C
-50..0 % TL_Thresh_Off
Service
-5%
Service
Pt100
Pt100
Pt1000
Ni1000
TempSensor
PressSensor
Pt100Pt1000
Pt100Ni1000
NoSensor
150°C/302°F
Service
150°C/302°
400°C/752°F
F
auto deact
Service
man deact
man deact
O2 guard
O2 control
conAutoDeac
auto deact
Service
man deact
man deact
O2 guard
O2 control
conAutoDeac
LMV51 LMV52
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
CC1P7550en