15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault Basic Unit
Page too long open
Page number
Internal Fault Basic Unit
Internal Fault Basic Unit
Page has an undefined status
Internal Fault Basic Unit
Page number
Parameter Set damaged
Last backup restore invalid (was
interrupted)
Internal Fault Basic Unit
Fault when copying a parameter page
Internal Fault Basic Unit
Number of parameter page
Internal Fault Basic Unit
Fault in connection with EEPROM
initialization
Meaning for the LMV5x system
Troubleshooting
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
Repeat backup restore
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
207/278