Siemens LMV5 Series Basic Documentation page 223

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A6
EF
LC
A6
F0
LC
A6
F1
LC
A6
F2
LC
A6
F3
LC
A6
F4
LC
A6
F5
LC
A6
F6
LC
A6
FE
LC
A6
FF
LC
A7
#
AZL
A7
01
AZL
A7
02
AZL
A7
04
AZL
A7
05
AZL
A7
07
AZL
A7
08
AZL
A7
09
AZL
A7
0A
AZL
A7
0B
AZL
A7
0C
AZL
A7
0D
AZL
A7
0E
AZL
A7
15
AZL
A7
16
AZL
A7
17
AZL
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault Load Controller
Invalid branch in eeprom module()
Internal Fault Load Controller
Fault during ROM test
Internal Fault Load Controller
Fault during RAM test
Internal Fault Load Controller
Fault during RAM test, register bank 0
Internal Fault Load Controller
Fault during RAM test, IDATA range
Internal Fault Load Controller
Fault during RAM test, XDATA range
Internal Fault Load Controller
Stack pointer does not point at stack
Internal Fault Load Controller
Stack overflow
Internal Fault Load Controller
Fault messages in fault management
Internal Fault Load Controller
Fault messages in fault management
AZL5...has detected own fault and
reported it to the basic unit.
Type of fault: See diagnostic code
Internal Fault AZL
CRC fault during ROM test
Internal Fault AZL
CRC fault during RAM test
Internal Fault AZL
Fault during key value check
Internal Fault AZL
Time block overflow
Internal Fault AZL
Sync fault or CRC fault
Internal Fault AZL
Fault main loop counter
Manual Lockout AZL
Fault message for emergency off function
via AZL...
Internal Fault AZL
Invalid AZL5... page
>250,000 startups, service required
Internal Fault AZL
Save fault parameter
Menu for Oil. Current Fuel is Gas Fuel changeover from oil to gas
Menu for Gas. Current Fuel is Oil Fuel changeover from gas to oil
Internal Fault AZL
CAN queue fault
Internal Fault AZL
CAN overflow fault
Internal Fault AZL
CAN busoff
Meaning for the LMV5x system
Troubleshooting
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
Observe instructions given below, and:
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective AZL...
Change to menu "GasSettings"
Change to menu "OilSettings"
223/278
CC1P7550en
01.10.2003