Siemens LMV5 Series Basic Documentation page 200

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
1E
01
SA
1E
02
SA
1E
04
SA
1E
08
SA
1E
10
FuM
1E
20
SA
1F
#
FuM
1F
01
FuM
1F
02
FuM
1F
03
FuM
1F
04
FuM
1F
05
FuM
1F
06
FuM
200/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Special Pos not reached
Positioning fault of air actuator
Special Pos not reached
Positioning fault of fuel actuator
Special Pos not reached
Positioning fault of auxiliary actuator 1
Special Pos not reached
Positioning fault of auxiliary actuator 2
Special Pos not reached
VSD has not reached the speed
Special Pos not reached
Positioning fault of auxiliary actuator 3
Code for VSD Module Fault
Basic unit has detected a fault in
connection with the VSD module
Speed Acquisition faulty
Internal VSD module test was not
successful
Wrong Direction of Rotation
Fan rotates in the wrong direction
Speed Acquisition faulty
Pulse sequence and length at the speed
input were different from those anticipated
Standardization canceled
Fan was not able to keep the standardized
because of VSD
speed at a constant level
Standardization canceled
Air actuator has not reached the prepurge
because of Air Actuator
position. For this reason, speed
standardization is not possible
Speed Test was not successfully
Internal VSD module speed test was not
completed
successful
Meaning for the LMV5x system
Troubleshooting
If fault occurs sporadically: Check CAN bus wiring.
Improve EMC.
If fault occurs constantly: Replace the defective basic unit
Check to see if the motor's direction of rotation is correct.
Check to see if the sensor disk on the motor is mounted the
correct way.
Change live conductor on the fan motor or check
parameterized direction of rotation on the VSD and correct,
if necessary
Check to see if sensor disk and speed sensor are correctly
mounted.
Check if the distance of the inductive sensor is correct.
Check if the inductive sensor is correctly connected
Check if motor runs.
Check if the inductive sensor is correctly connected.
Check if distance of inductive sensor is correct
Check to see if all air-influencing actuators travel to the
prepurge position.
Check to see if the relevant actuators are mechanically
overloaded or replace defective actuator, if necessary.
Check power supply to the actuators
CC1P7550en
01.10.2003