Siemens LMV5 Series Basic Documentation page 128

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1
Menu level 2
Menu level 3
128/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
PostpurgePosAu
x2
PostpurgePosAu
x3
PostpurgePosVS
D
ProgramStop
ResetIgnitPos
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux
IgnitionPosAux2
IgnitionPosAux3
IgnitionPosVSD
CurveParams
LoadLimits
MinLoadGas
MaxLoadGas
AuxActuator
AirActuator
Description
Postpurge position of auxiliary damper 2
Postpurge position of auxiliary damper 3
Postpurge position of VSD
Program stop
Resetting the ignition positions to invalid value
Setting the minimum and maximum load limits
Minimum load "Low fire" (gas)
Maximum load "High fire" (gas)
Auxiliary actuator for firing on gas: Deactivate / activate / VSD
operation
Air actuator for firing on gas: Deactivate / activate / air-
regulating
Value range
Access
Default
LMV51 LMV52
rights
parameter
setting
0..90°
Service
25°
0..90°
Service
25°
0..100%
Service
50%
deactivated
Service
deactivated
24 PrePurgP
32 PreP FGR
36 IgnitPos
44 Interv 1
52 Interv 2
72 PostPPos
76 PostPFGR
Service
Service
Service
Service
Service
Service
Service
Service
Service
0..MaxLoadGas
Service
0%
MinLoadGas..100 %
Service
100%
deactivated
OEM
deactivated
Damper act
VSD activat
deactivated
OEM
air influen
activated
air influen
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
CC1P7550en
01.10.2003