13.1 LMV5... and AZL5...
Mains voltage
Transformer AGG5.220
- Primary side
- Secondary side
Mains frequency
Power consumption (typically)
Safety class
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range (incl. mounting. plate)
Humidity
Condensation, formation of ice and ingress of water are not permitted!
Operating voltage
Power consumption (typically)
Degree of protection of housing
– Rear
– Front
Safety class
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range (incl. mounting plate)
Humidity
Condensation, formation of ice and ingress of water are not permitted!
Basic Documentation LMV51...
13 Technical data
AC 230 V -15 % / +10 %
AC 230 V
AC 12 V
2 x AC 12 V
50...60 Hz ±6 %
< 30 W
I with parts according to II and III as per
DIN EN 60 730-1
DIN EN 60 721-3-2
class 2K2
class 2M2
-20...+70 °C
< 95 % r.F.
DIN EN 60 721-3-3
class 3K5
class 3M2
-20...+60 °C
< 95 % r.h.
AC 24 V -15 % / +10 %
< 5 W
IP00, IEC 529
IP54, IEC 529 (when built in)
I with parts according to II and III as per
DIN EN 60 730-1
DIN EN 60 721-3-2
Class 2K3
Class 2M2
-20...+60 °C
< 95 % r.F.
DIN EN 60 721-3-3
Class 3K3
Class 3M2
-20...+60 °C
< 95 % r.F.