Siemens LMV5 Series Basic Documentation page 233

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
07
F1
BU
F2
#
BU
F2
07
BU
F2
08
BU
F2
0A
BU
F3
01
BU
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault Basic Unit
Internal fault calculation of precontrol.
Undefined value for a type of fuel
parameter
Code for faulty temperature values from
O2 module when calculating the air rate
change
Internal Fault Basic Unit
O2 module has delivered invalid value
Flue Gas Temp too high
Flue gas temperature outside the
permissible value range
QGO in Heating-up Phase
QGO probe not yet sufficiently heated up
Missing or faulty Control
PID parameter for controller algorithm
Parameters
missing
Meaning for the LMV5x system
Troubleshooting
Set permissible flue gas temperature to a higher level
Wait until probe has reached its operating temperature
Check controller parameters
*1)
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective module
*2)
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective module
233/278
CC1P7550en
01.10.2003