5.3.6 Commissioning Sensors

5.3.6.1 Setting and Adding a Smoke Detector (Connected to an AI/DI Port on
the ECC800-Pro)
If a smoke detector is installed, perform the following steps to configure it.
Context
If the detector is prefabricated, only check its settings.
Procedure
Step 1 Set smoke detector parameters.
1.
Issue 01 (2020-11-30)
Click Test Connect to check whether the UPS2000G-L connects to the
ECC800-Pro properly.
If the connection succeeds, click Confirm. The connected devices are displayed
in the Number of connected devices list.
If the connection fails, check whether the UPS2000G is properly connected to
the ECC800-Pro, whether the UPS2000G and ECC800-Pro are running properly,
and whether the parameter settings are consistent with the UPS2000G
parameters.
Log in to the ECC800-Pro WebUI as an administrator.
Copyright © Huawei Technologies Co., Ltd.
Parameter
Communications Port
Device Address
5 Power-On Commissioning
Setting
Select COM4 from the
drop-down list box.
NOTE
The setting example
indicates that the
UPS2000G is connected to
the COM4 port on the
ECC800-Pro. If the
UPS2000G is connected to
another port, enter the
number of the connected
port.
In this example, Device
Address is set to 1.
During actual
configuration, set the
device address for the
UPS2000G-L based on
the actual situation.
125