3.3.1 Application Conditions

Operating Environment
Table 3-6 Operating environment
Item
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Altitude
Table 3-7 Derating coefficients
Altitude
(m)
Air
volume
coefficie
nt
Cooling
capacity
coefficie
nt

3.3.2 Technical Specifications

Table 3-8 Technical specifications
Item
Power system
Refrigerant
Cooling capacity
Air supply mode
Issue 01 (2020-11-30)
0
1000
1500
1
0.887
0.835
1
0.940
0.909
Integrated Air Conditioner
220–240 V AC 50/60 Hz, 1 Ph
R410A
3.5 kW
Upward air supply and return at the indoor side,
and rear air return at the outdoor side
Copyright © Huawei Technologies Co., Ltd.
Integrated air conditioner
0–40°C
5%–95% RH (non-condensing)
–40°C to +70°C (without refrigerant)
–40°C to +55°C (with refrigerant)
5%–95% RH (non-condensing)
0–4000 m, derated at above 1000 m For details
about derating coefficients, see
2000
2500
0.785
0.737
0.878
0.846
a
3 System Architecture
Table
3-7.
3000
3500
4000
0.692
0.649
0.608
0.815
0.784
0.753