FusionModule500 Smart Mini Data Center
User Manual
Maintenance
Area
Intelligent lithium
battery
monitoring system
Water sensor and
water detection
cable
Issue 01 (2020-11-30)
Maintenance
Item
Battery
management
alarm
Cleanliness
Battery
connection
Measurement of
the ambient
temperature of
the intelligent
battery
monitoring system
Functions of the
water sensor and
water detection
cable
Copyright © Huawei Technologies Co., Ltd.
Operation
-
-
-
-
Place the water
detection cable
into the water
and check
whether a water
leakage alarm is
generated by the
water sensor.
Expected Result
Troubleshootin
g
No battery
Identify the
management
cause of an
alarm is
alarm based on
generated.
the alarm
information.
Wipe the battery
Remove dust.
surface using a
piece of white
paper and the
paper does not
turn black.
Battery terminals
Locate poor
and cables are in
contact points
good contact.
between battery
terminals and
cables.
The ambient
Locate the
temperature of
cause of an
the intelligent
abnormal
battery
temperature.
monitoring
system is lower
than 45°C.
A water leakage
If a water
alarm is
leakage alarm is
generated.
not generated,
replace the
water detection
cable.
6 O&M
184