Figure 5-8 DIP switch definitions for T/H sensors
Table 5-6 Setting device addresses
Address
1
2
Step 2 Add a T/H sensor.
1.
2.
Issue 01 (2020-11-30)
NO TE
Numbers 1 and 2 indicate the DIP switch settings of T/H sensors. The DIP switch of the T/H
sensor on the front door is set to 2, and that of the T/H sensor on the rear door is set to 1.
Toggle
Switch 1
ON
OFF
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Table 5-7 Adding a T/H sensor
Path
Parameter
Choose
Device
System
Attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device.
Communica
tions Port
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
5 Power-On Commissioning
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
Toggle
Switch 6
OFF
OFF