Step 2 Check the monitoring functions of smoke detector.
Table 5-5 Commissioning the detector
Check Method
Simulate a
smoky
environment
under the smoke
detector.
----End

5.3.6.2 Commissioning a T/H Sensor

Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port
on the T/H sensor, and the other end has been connected to the COM port on the
ECC800-Pro.
Procedure
Step 1 Set a device address for the T/H sensor.
Operate the DIP switch on the T/H sensor to set the device address for the sensor.
Toggle switches 1 to 6 specify the device address in binary mode. ON indicates 1,
and OFF indicates 0.
Issue 01 (2020-11-30)
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration tab page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Smoke
and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1
Port Settings.
Set Smoke sensor to Enable and click Submit.
Normal Connection Status
Smoke DI alarm is displayed
on the active alarm page of
the app or WebUI.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Alarm Clearance Method
Disconnect the smoke
detector cable and then
reconnect it to clear the
alarm.
126