FusionModule500 Smart Mini Data Center
User Manual
2.
3.
----End
4.2.5.3 Installing rPDUs
Context
Two rPDUs for horizontal installation are configured.
The two horizontal rPDUs need to be respectively installed at the 11th U and 13th
U positions at the rear door of the cabinet.
Procedure
Step 1 Open the rear door of the cabinet, and install floating nuts in the rPDU
installation position.
Step 2 Secure the horizontal rPDUs using screws.
Issue 01 (2020-11-30)
Install floating nuts at the busbar installation position.
Secure the busbar to the installation position using screws.
NO TE
The busbar needs to be installed at the 17th–18th U position. Determine the busbar
installation position based on the lithium battery configuration.
Figure 4-13 Installing busbars
Copyright © Huawei Technologies Co., Ltd.
4 Installation Guide
74