FusionModule500 Smart Mini Data Center
User Manual
Step 3 Power on the device.
1.
2.
----End

4.3 Cable Routing

4.3.1 System Cabling Rules

Attaching Cable Labels
A cable label must be consistent with the corresponding cabinet number.
Find the corresponding cable based on the wiring diagram in the cable fitting bag,
and attach the corresponding cable label taken out from the cable fitting bag to
both ends of the cable by wrapping the ends.
Attach the cable labels 20 mm away from the plug except for special
circumstances. For example, a label shall not be attached to the bending part of a
cable or attached in some positions that may affect cable installation. If a label
conflicts with a cable tie, attach the label to the outer side of the cable tie.
Attach labels to both ends of a cable.
Requirements for Neatly Routing and Binding Cables
To route and bind cables in an appealing way, follow these rules:
Issue 01 (2020-11-30)
the mounting ears on the front mounting bars of the cabinet, as shown in the
lower right figure.
Figure 4-47 Securing the device
Turn on the power switch.
Check the indicators on the front panel of the device for its running status.
NO TICE
NO TE
The cable labels must completely wrap the cable without wrinkles.