FusionModule500 Smart Mini Data Center
User Manual
Follow-up Procedure
If the hard disk works abnormally, contact Huawei technical support.

6.4.3.8 Replacing a T/H Sensor (33010516)

Prerequisites
Procedure
Step 1 Tap Shutdown on the controller home screen.
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Remove the cables from the T/H sensor.
After removing cables, wrap exposed terminals with insulation tape and do not
block cable labels. If cable labels are blocked, cables may be connected incorrectly
later.
Step 3 Remove the faulty T/H sensor.
Step 4 Attach the new T/H sensor to an appropriate position on the cabinet door frame
based on the site requirements.
Step 5 Reinstall the cable removed from the T/H sensor.
----End

6.4.3.9 Replacing a Smoke Detector

Prerequisites
Issue 01 (2020-11-30)
A T/H sensor needs to be replaced.
A spare T/H sensor of the same model is available and functional.
NO TICE
NO TICE
NO TE
Before removing a T/H sensor, remember the DIP switch setting on it. When you install a
new T/H sensor, you need to set the same DIP switch setting for the new one.
Recommended tools and materials: Phillips screwdriver, insulation tape, step
ladder (2 m)
A smoke detector needs to be replaced.
A spare smoke detector of the same model is available and functional.
Copyright © Huawei Technologies Co., Ltd.