2 CALCULATION OF SETTINGS
Table 2–9: GENERAL SETTINGS GUIDE (Sheet 2 of 3)
No.
Mnemonic
Description
OSC_GRAPHY
301
NUMFAULTS
Number of Fault Records
302
PREFAULT
Number of Pre-fault Cycles
303
SPLITREC
Splits Fault Record and
captures this percentage at
end, with 1-SPLITREC
captured at beginning
BRKR DUTY
401
E XP O N EN T
Exponent in I
402
MAX_OP
Maximum Number of
Breaker Operations for a
Breaker
403
MAX_IXT
Maximum Breaker Duty for a
Breaker
404
IXTPHASEA
Accumulated Breaker Duty,
Phase A
405
IXTPHASEB
Accumulated Breaker Duty,
Phase B
406
IXTPHASEC
Accumulated Breaker Duty,
Phase C
407
NUM_OP
Present Number of Breaker
Operations
407
NUM_OP_A
Present Number of Breaker
Operations for Phase A
408
NUM_OP_B
Present Number of Breaker
Operations for Phase B
409
NUM_OP_C
Present Number of Breaker
Operations for Phase C
INPUTS
501
C C 1
Contact Converter 1
502
CC2
Contact Converter 2
503
CC3
Contact Converter 3
504
CC4
Contact Converter 4
505
CC5
Contact Converter 5
506
CC6
Contact Converter 6
Setting/value is applicable to LPS-D Three Phase Tripping models only.
Setting/value is applicable to LPS-D Single Phase Tripping models only.
GE Power Management
Range (5A & 1A)
6, 12, 24, 36
1 to 8
0 to 100%
x
1.0 to 2.0
t calculation
0 to 9999
0 to 9999999 A
0 to 9999999 A
0 to 9999999 A
0 to 9999999 A
0 to 9999
0 to 9999
0 to 9999
0 to 9999
0 to 32
0 to 32
0 to 32
0 to 32
0 to 32
0 to 32
LPS-D Line Protection System
2.5 REFERENCE TABLES
Step
N/A
1
1
0.1
1
x
100
sec.
x
100
sec.
x
100
sec.
x
100
sec.
1
1
1
1
1
1
1
1
1
1
Default
N/A
5
2
0%
2.0
0
0
0
0
0
0
N/A
N/A
N/A
12
13
10
11
7
, 1
20
, 4
2-
71

Advertisement

Table of Contents