8.2 INFORMATION
This category is used to view the Station and Line ID strings which are set by the remote communications.
These Ids allow the user to easily identify each relay by name while logged in through communications. Use
the arrow keys to display the ID not currently on the screen.
NOTE: If the Station/Line ID string is longer than 20 characters, a check is made to see if the string can
be smoothly separated to fit on two lines. If it is not possible, the first 20 characters of the sta-
tion ID are displayed on the third line and the rest are displayed on the fourth line.
This category is used to display the Model and Version numbers for the relay.
This command can be used to trigger the immediate collection of oscillography data. Oscillography can be trig-
gered without at any privilege level. The user will be prompted to start the trigger.
Table 8–2: KEYPAD / DISPLAY INTERFACE ERROR MESSAGES
Error Message
VAL OUT OF RANGE
SETT NUM INVALID
Y/N NOT ENTERED
REQUEST INVALID
CATEGORY INVALID
8
BKR NUM INVALID
DATE INVALID
TIME INVALID
FAULT # INVALID
REMOTE LINK ACT
LUI KEY ERROR
ACT INVALID NOW
8-
26
OSC SNAPSHOT
Trigger Osc?
Cause of Error
The setting value is either greater than the upper limit or less than the lower
limit.
The setting number is not valid.
A YES or NO response key was required, but the [1/Y] or [3/N] key was not
pressed.
A key was pressed that is not valid for a sequence; for example:
The [ENT] key is pressed to view events.
The _ key is pressed during entry of a settings value.
An incorrect category number was entered for an action or information item.
A breaker number other than 1 or 2 was entered.
The day, month, or year entry is invalid.
The hour, minute, or seconds entry is invalid.
An out of range fault number was entered.
The remote communication link is in use for actions or settings; local settings or
changes can't be done.
The LUI received an invalid key code from the keyboard (hardware error).
The current action is invalid because the setting's CRC code is in error.
LPS-D Line Protection System
8 LOCAL USER INTERFACE
8.2.9 REQUEST STATION/LINE ID
8.2.10 REQUEST LPS-D MODEL/VERSION
8.2.11 OSCILLOGRAPHY SNAPSHOT