GE LPS-D Instruction Manual page 318

Line protection system
Table of Contents

Advertisement

13.2 DESIGN CONSIDERATIONS
Table 13–1: PICKUP DELAY TIMER TRUTH TABLE
S
L
13
X
X
X
d) COUNTERS
The counter has two input line, one output line, and a user selected count threshold (in milliseconds) as shown
in Figure 13–5: COUNTER. A transition from low (binary 0) to high (binary 1) on the S input line increments the
counter by a value of one. The O output line is high (binary 1) when the accumulated count is equal to or
greater than the count threshold. If the O output line is low (binary 0), then the accumulated count is less than
the set value. A transition from low (binary 0) to high (binary 1) on the R input line resets the counter to zero.
13-
4
S
R
Figure 13–4: PICKUP DELAY TIMER
R
Previous Timer State
L
NOT TIMING
L
NOT TIMING
L
TIMING DOWN
H
TIMING DOWN
NOT TIMING
S
R
Figure 13–5: COUNTER
LPS-D Line Protection System
1000
S O
R O
Current Timer State
NOT TIMING
TIMING DOWN
TIMER EXPIRED
TIMER RESET
NOT TIMING
5
0
0
0
0
13 XPRESSION BUILDER
RO
SO
RO
L
n-1
L
L
L
H
H
L
L
L
O