B.1 MEMORY MAPPING
Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R43066I
CC_12
R43070I
ACT_SET_GRP
R43071I
RESET_TYPE
B
R43079S32
STATION_ID
R43095S32
LINE_ID
R43120I
G1_Z1PHASE
R43121F
G1_Z1PHREACH
R43123F
G1_Z1PLEVDET
R43125I
G1_Z1GROUND
R43126F
G1_Z1GRDREACH
R43128I
G1_Z1GRDCHAR
R43129F
G1_Z1SUREACH
R43131F
G1_Z1GROUNDK0
R43133F
G1_Z1GLEVDET
R43135I
G1_Z1BLOCK
R43136I
G1_Z2PHASE
R43137F
G1_Z2PHREACH
R43139I
G1_Z2PCHARANG
R43140I
G1_Z2GROUND
R43141I
G1_Z2GRDCHAR
R43142F
G1_Z2GRDREACH
R43144I
G1_Z2GCHARANG
R43145I
G1_Z2TIMERS
R43146F
G1_Z2P_TIME
R43148F
G1_Z2G_TIME
R43150I
G1_Z3PHASE
R43151F
G1_Z3PHREACH
R43153I
G1_Z3PCHARANG
R43154I
G1_Z3GRND
R43155F
G1_Z3GRDREACH
R43157I
G1_Z3GCHARACHAG
R43158F
G1_Z3P_TIME
B-
6
(Sheet 2 of 27)
Contents
Units/Value/Range
CC_12
0 to 32
Active Settings Group
1 to 4
Reset Type
Station ID
Line ID
Z1PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z1PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1PLEVDET
0.0 to 9.9 p.u. V step 0.1
Z1GROUND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z1GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1GRDCHAR
0 = Mho; 1 = React
0.01 to 50.0 Ω step 0.01 (5A)
Z1SUREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1GROUNDK0
1.0 to 7.0 step 0.1
ZIGLEVDET
0.0 to 9.9 p.u. V step 0.1
Z1BLOCK
0 = No; 1 = Yes
Z2PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z2PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z2PCHARANG
90 to 120° step 5
Z2GROUND
0 = No; 1 = Yes
Z2GRDCHAR
0 = MHO; 1 = GDOC;
2 = MHOGDOC
0.01 to 50.0 Ω step 0.1 (5A)
Z2GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z2GCHARANG
90 to 120° step 5
Z2TIMERS
0 = No; 1 = Yes
Z2P_TIME
0.10 to 3.0 sec. step 0.01
Z2G_TIME
0.10 to 3.0 sec. step 0.01
Z3PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.1 (5A)
Z3PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z3PCHARANG
90 to 120° step 5
Z3GRND
0 = No; 1 = Yes
Z3GRDREACH
0.01 to 50.0 W step 0.1 (5A)
0.05 to 250.0 W step 0.05 (1A)
Z3CHARCHAG
90 to 120° step 5
Z3P_TIME
0.10 to 10.0 sec. step 0.01
LPS-D Line Protection System
APPENDIX B
R/W
Format
Code
R/W
INT
R/W
INT
R/W
F43
R/W
ASCII
R/W
ASCII
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
Float